devices (TEDs) while providing a ground through the ventilation module heat control circuits to the heat side of the TEDs. A pre-determined voltage
is also applied to the blower motors. The CCSM uses the following sequence, beginning with the Cool SoftStart Mode, to achieve the set point
temperature before it can enter the Open Loop Cool Mode.
-

Cool SoftStart Mode-The intent of the Cool SoftStart Mode is for the CCSM to bring the TED fin temperature to maximum cool temperate. The
CCSM does this by setting the blower motor speed control voltage to 0 volts, while ramping up the TED voltage duty cycle from 0 volts to
maximum voltage duty cycle over a period not to exceed 5 seconds. Then, with the TEDs at maximum voltage, the CCSM will increase the blower
speed to maximum voltage, and keep these settings for the MAX COOL DURATION. After which the system transitions to the Open Loop Cool
Mode.

-

Open Loop Cool Mode-At the completion of Cool SoftStart Mode, the CCSM will initiate Open Loop Cool Mode. The intent of this mode is to
maintain the set point fin temperature based on the input of the cool seat switch. First, by controlling the speed of the blower motor, then secondly,
by controlling TED voltage. The CCSM updates these voltages once every second.

FAULT STATE

The climate control seat system will operate normally in the battery voltage range of 9-16 volts. If the system voltage falls outside of this voltage
range, the module will shut down all outputs until the system returns to its normal operating voltage range. The system will also transition to the fault
state per the conditions listed below, by shutting down all outputs for the seat in which the fault occurred.

HIGH TEMPERATURE FAULT STATE

During the heating or cooling modes, if the TED temperatures listed below are exceeded for more than 4 seconds, the system will enter the High
Temperature Fault State. At which time the CCSM will set the TED voltage duty cycle to 0%, set the blower speed control to maximum voltage to
blow ambient air over the TEDs, attempting to reduce the TED temperature below the listed maximums. The system will operate in this mode for 30
seconds
. If the over temperature fault still exists after 30 seconds, the system will transition to the FAULT state for the remainder of the ignition cycle.
If the over temperature fault clears, the system will then transition to the appropriate heat or cool softstart mode. The following temperatures are based
upon individual readings of either sensor:
-

Heat mode TED temperature exceeds 230°F (110°C).

-

Cool mode TED temperature exceeds 149°F (65°C).

TEMPERATURE DELTA FAULT

During the heating or cooling modes, if the climate control seat module (CCSM) detects a temperature difference between the seat cushion and seat
back TED temperature sensors exceeding the delta temperature listed below for more than 4 seconds, the system will enter the Temperature Delta
Fault state. At which time the CCSM will set the TED voltage duty cycle to 0%, set the blower speed control to maximum voltage to blow ambient air
over the TEDs, attempting to reduce the delta temperature to less than 68°F. The system will operate in this mode for 30 seconds. If the delta
temperature fault still exists after 30 seconds, the system will transition to the FAULT state and remain there until the ignition has been set to OFF.
-

Delta between the seat cushion and seat back temperature sensors is 104°F (40°C).

-

This fault state is disabled in the back only mode.