Refrigerant: Service and Repair
HVAC Systems - Automatic

Successful Transfer Complete

IMPORTANT:  If the transfer of refrigerant stops before complete, refer to Unsuccessful Transfer.

1. Close the high-side valve on the unit control panel. Both valves should now be closed
2. Start the engine. Turn ON the A/C system and let the system run until the readings on the high-side and low-side gauges stabilize.

Compare the readings, the outlet temperatures, the ambient temperature, and the humidity to the A/C performance table. Refer to System
Performance Test.

3. With the A/C system running, close the high-side coupler valve.

Disconnect the high-side (red) hose from the vehicle.

4. Open the high-side and the low-side valves on the control panel.
5. Refrigerant from both hoses will be drawn quickly into the A/C system through the low-side (blue) hose.
6. Close the low-side coupler valve and disconnect the valve from the vehicle.

Unsuccessful Transfer

On rare occasions, the total charge does not transfer to the vehicle A/C system. This can occur for the following reasons:

1. If the transfer is too slow because the pressure in the tank unit and the vehicle A/C system are about the same, the unit emits an audible signal and

the display shows the weight remaining for transfer. When this happens, do the following steps:
1.1. Close the high-side valve.
1.2. Open the low-side valve.
1.3. Start the vehicle A/C system. Press HOLD/CONT on the keyboard. This will put the remainder of the charge in the A/C system.
1.4. Continue with the Successful Transfer Complete procedure.

2. If the transfer will not complete and the display shows CHECK REFRIGERANT, there is not enough refrigerant in the tank to complete the

process. This condition requires the recovery of the partial charge of refrigerant in the vehicle A/C system, and another complete evacuation and
charge procedure.
2.1. Press HOLD/CONT on the keyboard in order to interrupt the cycle.
2.2. Press RESET in order to reset this unit.
2.3. Recover the refrigerant that has been charged into the system.

3. Following the manufacturers instructions, add refrigerant to the tank and refer to Evacuation.