cadillac Workshop Repair Guides

Cadillac Workshop Service and Repair Manuals

Diagram Information and Instructions|Page 9035 > < Diagram Information and Instructions|Page 9033
Page 10
background image

checking the box under Selected. At the bottom of the graph there are four functions Zoom In (increase size), Zoom Out (decrease size),
Bookmarks, and Pause Scrolling. Each of these functions can be accessed by clicking on them.

Testing for Continuity

Testing for Continuity

Caution:  Refer to Test Probe Caution   (See: Service Precautions/Vehicle Damage Warnings/Test Probe Caution).

The following procedures verify good continuity in a circuit.

With a DMM

1. Set the rotary dial of the DMM to the ohm position.
2. Disconnect the power feed (i.e. fuse, control module) from the suspect circuit.
3. Disconnect the load.
4. Press the MIN MAX button on the DMM.
5. Connect one lead of the DMM to one end of the circuit to be tested.
6. Connect the other lead of the DMM to the other end of the circuit.
7. If the DMM displays low or no resistance, the circuit has good continuity.

With a Test Lamp

Note:  Only use the test lamp procedure on low impedance power and ground circuits.

1. Remove the power feed (i.e. fuse, control module) from the suspect circuit.
2. Disconnect the load.
3. Connect one lead of the test lamp to one end of the circuit to be tested.
4. Connect the other lead of the test lamp to battery positive voltage.
5. Connect the other end of the circuit to ground.
6. If the test lamp illuminates (full intensity), then the circuit has good continuity.

Testing for Electrical Intermittents

Testing for Electrical Intermittents

Special Tools

EL-39200 Digital Multimeter

For equivalent regional tools, refer to Special Tools   (See: Power and Ground Distribution/Tools and Equipment).

Perform the following procedures while wiggling the harness from side to side. Continue this at convenient points (about 6 inches apart) while watching
the test equipment.

*

Testing for Short to Ground   (See: Testing and Inspection/Component Tests and General Diagnostics/General Electrical Diagnostic
Procedures/Circuit Testing/Testing for Short to Ground)

*

Testing for Continuity   (See: Testing and Inspection/Component Tests and General Diagnostics/General Electrical Diagnostic Procedures/Circuit
Testing/Testing for Continuity)

*

Testing for a Short to Voltage   (See: Testing and Inspection/Component Tests and General Diagnostics/General Electrical Diagnostic
Procedures/Circuit Testing/Testing for a Short to Voltage)

If the fault is not identified, perform the procedure below using the MIN MAX feature on the Digital Multimeter (DMM). This feature allows you to
manipulate the circuit without having to watch the DMM. The DMM will generate an audible tone when a change is detected.

Note:  The DMM must be used in order to perform the following procedure since the DMM can monitor current, resistance or voltage while recording
the minimum (MIN), and maximum (MAX) values measured.

1. Connect the DMM to both sides of a suspected connector (still connected), or from one end of a suspected circuit to the other. Refer to

Troubleshooting with a Digital Multimeter   (See: Testing and Inspection/Component Tests and General Diagnostics/General Electrical Diagnostic
Procedures/Circuit Testing/Troubleshooting with a Digital Multimeter) for information on connecting the DMM to the circuit.

2. Set the DMM to the V (AC) or V (DC) position.
3. Select the voltage range feature of the DMM in order to select the desired voltage range.
4. Select the MIN MAX function of the DMM. The DMM displays 100 ms RECORD and emits an audible tone (beep). 

Note:  The 100 ms RECORD mode is the length of time an input must stay at a new value in order to record the full change.

Diagram Information and Instructions|Page 9035 > < Diagram Information and Instructions|Page 9033