FAIL CODES/LEVEL DISPLAY

Fail Codes/Level are displayed using the REAR WIPER and INTERMITTENT LED's flashing in sequence. The REAR WIPER LED represents
the Level and the INTERMITTENT LED represents the Value. After Calibration/Diagnostics is completed, the control will begin flashing Level 1
codes. Depressing the WASH button will cycle to Level 2, depressing WASH again will cycle to Level 3. Each time the WASH button is
depressed will cycle to the next level. After Level 5 is reached, you will cycle back to Level 1. 

Failure Code Levels -- Wipe Button LED

Level Display

1

Fail Codes

2

Mode Potentiometer Test

3

Blend/Pass. Potentiometer Test

4

Evaporator Probe (A/C and Zone Units Only)

5

Driver Potentiometer (Zone Units Only)

Level 1 Failure Codes -- Intermittent Wipe Button LED

Code Definition

0

Passed ALL Tests

1

Mode Actuator Did Not Reach Defrost Position

2

Mode Actuator Did Not Reach Panel Position

3

Blend/Pass Actuator Did Not Reach Cold Stop

4

Blend/Pass Actuator Did Not Reach Heat Stop

5

Evaporator Probe Open

6

Evaporator Probe Shorted

7

Driver Actuator Did Not Reach Cold Stop

8

Zone/Driver Actuator Did Not Reach Heat Stop

9

Control Head Internal Failure

NOTE:  If the Control is a Heater Only you will only cycle from Levels 1 to 3.

TEMPERATURE AND MODE POTENTIOMETER DIAGNOSTICS

A/C Units
The Temperature and Mode Potentiometer can be tested after calibration is complete by pressing the WASH button and cycling to Levels 2, 3 or 5
as displayed by the REAR WIPER LED. INTERMITTENT LED flash rate will change as the Temperature or Mode potentiometer is moved from
one end to the other.

Heater Only Units
On Heater Only units you can only cycle to Levels 2 and 3. In each individual test the INTERMITTENT LED flash rate will change as the
Temperature or Mode potentiometer is moved from one end to the other.

EVAPORATOR PROBE TEMPERATURE DIAGNOSTICS

The evaporator probe can be tested by using the INTERMITTENT LED to display the actual temperature the sensor is reading. The HVAC
control module can only display temperatures from 1 to 99 degrees. To read the temperature, perform the following:
-

Set Blower motor to any speed other than OFF

-

Set A/C to ON, if A/C Clutch does not engage make sure Fail Codes 5 and 6 are cleared.To clear the error code 5 and 6 the evaporator probe
and/or the wiring repair needs to be completed. Then, press and hold the intermittent wipe button for 5 seconds.

-

Run Diagnostics (Depress REAR WIPER and REAR WASH)

-

When Diagnostics is complete, Cycle to Level 4.

Display Sequence is as follows:
-

REAR WIPER LED will display the Level

-

INTERMITTENT LED will display ten's digit

-

Short Pause

-

INTERMITTENT LED will display the one's digit.

The HVAC control module will continue to cycle the Level and then Temperature until the level is changed or Calibration Diagnostics and
Cool-down test is exited.

A/C and Recirc LED's Flashing Simultaneously

FAILED COOL-DOWN TEST.

1. Determine if the refrigerant system is operating correctly:

-

Check the outlet air temperature

-

Feel the compressor suction plumbing, is it hot?

2. If not OK, go to Step 3. If OK, repeat the Calibration Diagnostic and Cool-down test.
3. If system does not seem to be operating correctly, perform diagnostics for poor performance: