gmc Workshop Repair Guides

GMC Workshop Service and Repair Manuals

Diagram Information and Instructions|Page 24 > < Diagram Information and Instructions|Page 22
Page 7
background image

future reference.

A DMM should be used instead of a test lamp in order to test for voltage in high impedance circuits. While a test lamp shows whether voltage is present,
a DMM indicates how much voltage is present.

The ohmmeter function on a DMM shows how much resistance exists between 2 points along a circuit. Low resistance in a circuit means good
continuity.

IMPORTANT:  Disconnect the power feed from the suspect circuit when measuring resistance with a DMM. This prevents incorrect readings. DMMs
apply such a small voltage to measure resistance that the presence of voltages can upset a resistance reading.

Diodes and solid state components in a circuit can cause a DMM to display a false reading. To find out if a component is affecting a measurement take a
reading once, then reverse the leads and take a second reading. If the readings differ the solid state component is affecting the measurement.

Following are examples of the various methods of connecting the DMM to the circuit to be tested:

-

Backprobe both ends of the connector and either hold the leads in place while manipulating the connector or tape the leads to the harness for
continuous monitoring while you perform other operations or test driving. Refer to Probing Electrical Connectors.

-

Disconnect the harness at both ends of the suspected circuit where it connects either to a component or to other harnesses.

-

If the system that is being diagnosed has a specified pinout or breakout box, it may be used in order to simplify connecting the DMM to the circuit
or for testing multiple circuits quickly.

Troubleshooting With A Test Lamp

TROUBLESHOOTING WITH A TEST LAMP

TOOLS REQUIRED

J 34142- B 12-Volt Unpowered Test Lamp

NOTE:  Refer to Test Probe Notice in Service Precautions.

A test lamp can simply and quickly test a low impedance circuit for voltage.

The J 34142- B is Micro-Pack compatible and comprised of a 12-volt light bulb with an attached pair of leads.

To properly operate this tool use the following procedures.
1. Attach 1 lead to ground.
2. Touch the other lead to various points along the circuit where voltage should be present.
3. When the bulb illuminates, there is voltage at the point being tested.

Using Connector Test Adapters

USING CONNECTOR TEST ADAPTERS

NOTE:  Do not insert test equipment probes into any connector or fuse block terminal. The diameter of the test probes will deform most terminals. A
deformed terminal can cause a poor connection, which can result in system failures. Always use the J 35616-B Connector Test Adapter Kit or the J
42675 Flat Wire Probe Adapter Kit in order to frontprobe terminals. Do not use paper clips or other substitutes as they can damage terminals and cause
incorrect measurements.

Using Fused Jumper Wires

USING FUSED JUMPER WIRES

TOOLS REQUIRED

J 36169-A Fused Jumper Wire

IMPORTANT:  A fused jumper may not protect solid state components from being damaged.

The J 36169-A includes small clamp connectors that provide adaptation to most connectors without damage. This fused jumper wire is supplied with a 
20-A fuse which may not be suitable for some circuits. Do not use a fuse with a higher rating than the fuse that protects the circuit being tested.

Connector Position Assurance Locks

CONNECTOR POSITION ASSURANCE LOCKS

The connector position assurance (CPA) is a small plastic insert that fits through the locking tabs of all the SIR system electrical connectors. The CPA
ensures that the connector halves cannot vibrate apart. You must have the CPA in place in order to ensure good contact between the SIR mating
terminals.

Terminal Position Assurance Locks

Diagram Information and Instructions|Page 24 > < Diagram Information and Instructions|Page 22