background image

5420 and a 900 angle gage Adapter J 9459 is available.

Wear J 5453 Safety Goggles and wrap a clean cloth around fittings and connections.

-

Discharge the system before removing and replacing refrigeration lines or components.

-

Use the service valve and pressure gage sets during evacuation and charging procedures.

-

Do not charge while the compressor system is hot.

-

Always discharge the system at the low side service fitting and perform the entire evacuation and charging procedure through the low side
service fitting.

-

Do not connect the high pressure line or any line to the high side service fitting during discharging and charging procedures.

WARNING:  Never remove a gage line from its adapter when the line is connected to the system. Always remove the line adapter from
the service fitting to disconnect a line. Do not remove charging hose at gage set while attached to service low side fitting. This will
discharge the system due to the depressed schrader valve in service low side fitting and may cause personal injury due to escaping 
Refrigerant-12.