Accord L4-1829cc 1.8L SOHC ES, ET FI (1985)
A/C Thermostat: Testing and Inspection
A/C THERMOSTAT TEST
-
Dip the thermostat capillary tube into a pan filled with ice water, and check for continuity.
Cutoff 1.5 - 0.5°C (35 - 33°F)
Cutin 2.5 - 5.0°C (37 - 41°F)
-
If cut-off or cut-in temperature is too low or too high, replace the thermostat.