CR-V EX 4WD L4-1972cc 2.0L DOHC MFI (2000)
-
Release the field coil connector from the holder, then disconnect it. Check the thermal protector for continuity. If there is no continuity, replace the
thermal protector.
NOTE: The thermal protector will have no continuity above 251.6 to 262.4°F (122 to 128°C). When the temperature drops below 240.8 to 219.8
°F (116 to 104°C), the thermal protector will have continuity.
-
Check resistance of the field coil.
Field Coil Resistance: 3.2 ± 0.15 ohms at 68°F (20°C)
If resistance is not within specifications, replace the field coil.