Discharge Air Temperature Sensor / Switch: Testing and Inspection
INSPECTION
INSPECT DUCT TEMPERATURE SENSOR
a. Remove the air duct sensor.
b. Measure the resistance according to the value(s) in the table.
NOTE:
-
Touching the sensor even slightly may change the resistance value. Hold the connector of the sensor.
-
When measuring the resistance, the sensor temperature must be the same as the ambient temperature.
HINT: As the temperature increases, the resistance decreases (see the graph).