H2-H3

Normal Operation

The SJB communicates with the diagnostic tool through the medium speed controller area network (CAN), circuits VDB06 (GY/OG) and VDB07
(VT/OG). The SJB and instrument cluster share network termination responsibilities with the use of a split termination resistor in each module. Check
the medium speed CAN circuits between the SJB C2280d and the data link connector (DLC) C251. The total resistance values must not be more than 
5 ohms. If the resistance is more than 5 ohms there is an open in one of the high speed CAN circuits, damage to the DLC C251, damage to the SJB
C2280d, or a problem in an in-line connector.

Possible Causes

-

medium speed CAN data plus circuit VDB06 (GY/OG) open

-

medium speed CAN data minus circuit VDB07 (VT/OG) open

-

SJB C2280d

-

SJB

Test I: The Parking Aid Module Does Not Respond To The Diagnostic Tool

PINPOINT TEST I: THE PARKING AID MODULE DOES NOT RESPOND TO THE DIAGNOSTIC TOOL