Refrigerant Pressure Sensor / Switch: Testing and Inspection

Dual Pressure Switch Testing

1. Disconnect the dual pressure switch connector.
2. Using a jumper wire, connect the terminal on the pressure wiring harness.
3. Connect an ohmmeter to the pressure switch terminals.
4. Install a manifold gauge set to the high side service port.
5. Operate the air conditioning system and check for switch continuity at the specified pressure.

High/Low Pressure Side

PRESSURE INCREASING

OHMMETER READING

33 PSI

Continuity

384 PSI

No continuity

PRESSURE DECREASING

OHMMETER READING

299 PSI

Continuity

30 PSI

No continuity

6. If there is no continuity, replace the switch.