Refrigerant Oil: Service and Repair
Maintaining Chemical Stability In the Refrigeration System

General Information

The efficient operation and life of the air conditioning system is dependent upon the chemical stability of the refrigeration system. When foreign
materials, such as dirt, air, or moisture, contaminate the refrigeration system, they will change the stability of the R-134a and viscosity of refrigerant oil.
They will also effect pressure-temperature corrosion and abnormal wear of moving parts.

Adding Oil

Adding oil to the A/C system should take place after recovery and before evacuation procedure. Open the A/C system at the suction/liquid line assembly
to liquid line joint. Always install new seal washers whenever a joint is opened. Do not lubricate seal washers. Pour the correct quantity of new PAG
compressor oil into the liquid line. For component replacement, add new Saturn refrigerant PAG oil to the component before installation.

Oil Distribution

Saturn air conditioning system requires 220 ml (7.5 oz.) of PAG compressor oil. Service compressors have 220 ml (7.5 oz.) of PAG oil installed.

New oil quantities must be added to system during component replacement and conditions stated as follows:

With no signs of excessive oil leakage, add:

A. Compressor: Remove, drain, and measure oil. Drain replacement compressor. Add the same amount of new PAG compressor oil drained from

removed compressor to replacement compressor. See Compressor for details.

B. Evaporator: Add 72 ml (2.4 oz.) of new PAG compressor oil.
C. Condenser: Add 38 ml (1.3 oz.) of new PAG compressor oil.
D. Receiver-dehydrator: Add 11 ml (.4 oz.) of new PAG compressor oil.

Refrigerant Oil Loss Due to A Large Leak

If the refrigerant charge is abruptly lost due to a large refrigerant leak, (hose rupture or collision) approximately 132 ml (4.5 oz.) of refrigerant oil will be
carried out of the system suspended in the refrigerant. Any failure that caused an abrupt refrigerant discharge will cause this oil loss. Conditions that
allow the refrigerant to seep or bleed off over time do not cause this oil loss.

Upon replacement of a component which caused a large refrigerant leak, add 132 ml (4.5 oz.) of new PAG compressor oil plus the required amount of
oil for the particular component (as outlined previously).

Add the oil directly to the replaced component if possible. If the oil cannot easily be added to the replaced part, add the oil to the liquid line (as outlined
previously).