Possible deviation from specification | Possible cause of fault | Rectifying fault |
l
| High pressure increases beyond the specification, |
l
| Low pressure falls quickly to the diagram value or lower, |
l
| the required cooling power is not delivered. |
| Restriction or obstruction in the refrigerant circuit. | –
| Feel the refrigerant circuit with the hand to sense the temperature gradient. |
l
| At one component a temperature gradient will be detected: |
–
| If a hose or pipe is kinked or crushed, renew it. |
–
| In case of an obstruction, flush refrigerant circuit with compressed air and nitrogen. |
l
| If no faults are found: |
–
| Rinse (clean) refrigerant circuit → Chapter. |
|
l
| High pressure and low pressure are normal at first, but after a time, |
l
| the high pressure increases beyond the specified value, |
l
| the low pressure falls to the diagram value or lower, |
l
| the cooling power called for is not delivered. |
| Moisture in the refrigerant circuit. | –
| Flush refrigerant circuit with compressed air and nitrogen. |
–
| Repeat the check; if the system does not operate correctly |
–
| Rinse (clean) refrigerant circuit → Chapter. |
–
| Recharge refrigerant circuit. |
|
l
| Low pressure is too low (see diagram), |
l
| the cooling power called for is delivered. |
| The air conditioner compressor is defective. | –
| Rinse (clean) refrigerant circuit → Chapter. |
–
| Renew air conditioner compressor. |
|