Octavia Mk2
|
Note
|
Possible deviation from the specified value | Possible cause of fault | Rectifying fault | ||||||||||||||||||
|
|
| ||||||||||||||||||
|
| |||||||||||||||||||
|
|
Note
t | If no fault is found for this complaint, clean the refrigerant circuit → Chapter. |
t | Check the measured values of the evaporator vent temperature sender -G263- and the actuation of the regulating valve for compressor of air conditioning system -N280-. If the measured value of the evaporator vent temperature sender -G263- is incorrect, the evaporator can ice up and the cooling capacity is not reached. |
t | If the function of the air conditioning system is not O.K. when repeating the test after replacing the expansion valve (reexchange expansion valve), clean refrigerant circuit → Chapter. Subsequently replace AC compressor and fluid reservoir with dessicator or only dessicator (specifically designed for vehicles). |
t | If the expansion valve is defective (it is closed constantly or it does not open up wide enough) the regulating valve for compressor of air conditioning system -N280- is actuated to maximum performance and the low pressure drops to the diagram value or lower (the AC compressor suctions the refrigerant out of the low pressure side). As no refrigerant can flow through the expansion valve, the cooling capacity is not reached, perhaps the high pressure does not rise or only rises slightly because no energy turnover exists. |
t | If this fault occurs, it can happen that the evaporator ices up although the volume of refrigerant in the circuit is O.K. |
Possible deviation from the specified value | Possible cause of fault | Rectifying fault | ||||||||||||||||
|
|
|
Possible deviation from the specified value | Possible cause of fault | Rectifying fault | ||||||||||||||||||||||||||||
|
|
|
Note
t | If this fault occurs, it can happen that the evaporator ices up although the volume of refrigerant in the circuit is O.K. |
t | If the expansion valve is defective (it is closed constantly or it does not open up wide enough) the regulating valve for compressor of air conditioning system -N280- is actuated to maximum performance and the low pressure drops to the diagram value or lower (the AC compressor suctions the refrigerant out of the low pressure side). As no refrigerant can flow through the expansion valve, the cooling capacity is not reached, perhaps the high pressure does not rise or only rises slightly because no energy turnover exists. |
Possible deviation from the specified value | Possible cause of fault | Rectifying fault | ||||||||||||||||||
|
|
| ||||||||||||||||||
|
|
Note
t | If problems arise due to humidity in the refrigerant circuit only after a longer operating time or only occasionally (the low pressure drops below the specified value and the evaporator ices up), it is adequate to replace the dessicator (the volume of refrigerant oil must be adapted → Chapter). Subsequently the refrigerant circuit must be evacuated for at least 3 hours. |
t | First of all, it is not required to clean the refrigerant circuit for this complaint (to flush with refrigerant R134a or to blow through with compressed air and nitrogen), as normally only a small amount of humidity is present in the system which can be removed through a longer period of evacuation. |
t | If this fault occurs, it can happen that the evaporator ices up although the volume of refrigerant in the circuit is O.K. |
t | Due to a fault on the evaporator vent temperature sender -G263- the refrigerant circuit can also ice up. For this complaint, also observe the measured value of this sender → Vehicle diagnostic tester |
Possible deviation from the specified value | Possible cause of fault | Rectifying fault | ||||||||||||||||||
|
|
|
Note
t | If the fault „high pressure is normal, low pressure is too low“ occurs, please observe the following: If this fault occurs it can happen that the evaporator ices up although the volume of refrigerant in the circuit is O.K. |
t | If the fault occurs on the regulating valve for compressor of air conditioning system -N280- (the regulating valve is not actuated and the AC compressor however keeps running) it is not required to clean the refrigerant circuit (flush with refrigerant R134a or blow through with compressed air and nitrogen). If this fault occurs, it is sufficent to replace the AC compressor (adapt the volume of refrigerant oil in the new AC compressor → Chapter). |
t | If the expansion valve is defective (it is closed constantly or it does not open up wide enough) the regulating valve for compressor of air conditioning system -N280- is actuated to maximum performance and the low pressure drops to the diagram value or lower (the AC compressor suctions the refrigerant out of the low pressure side). As no refrigerant can flow through the expansion valve, the cooling capacity is not reached, perhaps the high pressure does not rise or only rises slightly because no energy turnover exists. |
t | Due to a fault on the evaporator vent temperature sender -G263- the refrigerant circuit can also ice up. Also observe the measured value of this sender → Vehicle diagnostic tester |
Possible deviation from the specified value | Possible cause of fault | Rectifying fault | ||||||||||||||||||||||||||||||
|
|
| ||||||||||||||||||||||||||||||
|
|
Note
The cause of this fault may also be a surplus of refrigerant oil in the circuit. Over-filling with refrigerant oil can occur if, for example, the AC compressor was replaced without adapting the volume of refrigerant oil. |
Possible deviation from the specified value | Possible cause of fault | Rectifying fault | ||||||||||||||||
|
|
| ||||||||||||||||
|
|
Note
t | Over-filling with refrigerant oil can occur if, for example, the AC compressor was replaced without adapting the volume of refrigerant oil. |
t | If the expansion valve is defective (always open), the evaporator temperature is no longer regulated in such a way that only gaseous refrigerant leaves the evaporator. Under certain operating conditions, liquid drops can then be sucked into the AC compressor, this then leads to noises (liquid cannot be compressed). |