Pressures and temperatures in the refrigerant circuit and its arrangement > < General instructions for refrigerant circuit
Pressures, temperatures and arrangement of the refrigerant circuit with expansion valve
   
Pressures, temperatures and arrangement of the refrigerant circuit with expansion valve
ComponentAggregate state of refrigerantPressure (bar overpressure)Temperature in Celsius
Evaporator -13-, from inlet to outletVapourapprox. 1.2 bar1)approx. -7 °C 2)
Expansion valve -12-Liquid, released in vapourapprox. 14 barapprox. +55°C (high pressure side), reduced to -7°C (low pressure side)
High pressure switch / high pressure sender -6-Liquidapprox. 14 barapprox. +55 °C
Service connection - high pressure side -10- and fluid reservoir -9-Liquidapprox. 14 barapprox. +55 °C
Condensor -8-from gas (at the inlet) via vapour to liquid (at the outlet)approx. 14 barfrom approx. +65°C (at the inlet) to approx. +55°C (at the outlet)
Pressure relief valve -5- and air conditioning compressor - high pressure side Gasapprox. 14 barapprox. +65 °C
Air conditioning compressor - low pressure sideGasapprox. 1.2 bar1)approx. -1 °C 2)
Service connection - low pressure side -14-Gasapprox. 1.2 bar1)approx. -1 °C 2)

1) In refrigerant circuits with regulated AC compressor, the pressure is maintained at approx. 2 bar absolute pressure (corresponds to approx. 1 bar overpressure) despite the varying heat transfer and different engine speeds. This is only valid within the performance range of the AC compressor; in the event the performance range of the AC compressor is exceeded, the pressure rises → Chapter.
2) In refrigerant circuits with regulated AC compressor, the temperature is maintained within the performance range of the AC compressor despite the varying heat transfer and different engine speeds. This is only valid within the performance range of the AC compressor. If the performance ranges of the AC compressor are exceeded, the temperature rises → Chapter.
   
HP = High-pressure side
LP = Low-pressure side
1 - Regulating valve for compressor of air conditioning system - N280-
2 - Compressor
3 - Belt pulley
q   with anti-lock device
4 - Oil drain plug
5 - Pressure relief valve
6 - High-pressure sender -G65-
7 - Connection with valve
8 - Condenser
9 - Fluid reservoir with dessicator
10 - Extractor, filler and measurement valve
q   High-pressure side
11 - Screw cap
12 - Expansion valve
13 - Evaporator
14 - Extractor and measurement valve
q   Low-pressure side
15 - Screw cap
16 - Shock absorber
q   for damping of pressure fluctuations
q   only fitted on certain models

   

Pressures and temperatures in the refrigerant circuit and its arrangement > < General instructions for refrigerant circuit