Air Door Actuator / Motor: Customer Interest
A/C - Insufficient Cooling

Subject:

Fresh air/recirculation servo mount, repairing

Model(s):  5000 1984-1988 m.y. 100/200 From 1989 m.y.
Group:

87

Number:

90-01

Date:

November 30, 1990

insufficient A/C cooling can be the result of a broken fresh air/recirculation servo mount caused by a torn, distorted, or shifted recirculation air flap seal.

A misaligned seal exposes seal adhesive, and causes the recirculation flap to stick. The added force required to open the flap causes the servo mount to
break.

Use the following procedure to repair a broken or cracked fresh air/recirculation servo mount.

Parts required
Description

Part No.

Quantity

Bracket

200 271 200

1

Screw, (4.2 X 13) 
self-tapping

N 013 966.12

2

Seal

433 271 263 A

1

CAUTION

Part numbers are for reference only. Always check with your Parts Department for latest parts information.

^

remove glove compartment

^

remove glove compartment liner, if equipped

^

remove passenger side lower shelf