Additional heater
Checking and adjusting CO2-content in additional heater exhaust gas
Checking and adjusting CO2-content in additional heater exhaust gas

Notes:

  • ◆ The CO2-content in the exhaust gas can be adjusted in the "10 Adaption" function via the channel number "02".
  • ◆ The actuation curve for the combustion air blower -V6 (and thus the delivery performance) is changed via the adaption via the control unit.

Test requirements

  • ‒ The coolant temperature is lower than 30 °C. at the start of the test
  • ‒ The ambient temperature is less than 20 °C.
  • ‒ Battery -A is sufficiently charged.
  • ‒ If the fault memory was interrogated =>Page 01-24 and any displayed faults rectified.
  • ‒ The fuel tank is sufficiently full (fuel gauge in the dash panel insert is not in the red area).