Control sequence at low ambient temperatures > < Auxiliary heater components
Control sequence on start-up of auxiliary heater (also as supplementary heater)
   
Control sequence on start-up of auxiliary heater (also as supplementary heater)

A = ON signal for auxiliary heater (supplementary heater)
–  The auxiliary heater control unit -J364- receives the request for activation as auxiliary heater (or supplementary heater) via the convenience data bus.
a = Component check (approx. 2 seconds)
–  The auxiliary heater control unit -J364- checks the connected components
B = Pre-heating
b = Pre-heating time (approx. 6 seconds)
C = Run-up
c = Pre-heating and ventilation (approx. 7 seconds)
D = Start of fuel delivery
d = Start and flame formation (max. 90 seconds)
–  If no flame is detected, the auxiliary heater control unit -J364- terminates the starting procedure. On completion of the run-on time stored in the auxiliary heater control unit -J364-, the auxiliary heater control unit -J364- attempts a second start. If there is again no flame, the auxiliary heater control unit -J364- switches to fault status.
E = Flame is detected
e = Safety margin (approx. 6 seconds)
–  For flame stabilisation
F = Start of full load operation
–  Full load operation (duration temperature-dependent)
f 1 = The coolant temperature in the auxiliary heater reaches 30 °C (up to 45 °C depending on the version of the auxiliary heater control unit -J364-) and, in auxiliary heating mode, the operating and display unit, Climatronic control unit -J255- of the air conditioner/heater is requested by way of the convenience data bus system to switch on the fresh air blower -V2-.
–  At the start of full load operation, the heater coolant shut-off valve -N279- is actuated and, given a low coolant temperature, the coolant circuit is switched to the small circuit.
f 2 = The coolant temperature in the auxiliary heater reaches 71 °C, the auxiliary heater control unit -J364- alters actuation of the heater coolant shut-off valve -N279- → Chapter
   

Control sequence at low ambient temperatures > < Auxiliary heater components