2 RA Leak-testing Evaporator > < 1 RA Leak-testing Condenser|Page 2979
Page 3
background image

Set test pressure of 10 bar is only permitted to drop by 2 bar to
8.5 bar over a test period of 1.5 hours.

If the pressure loss is greater than 1.5 bar, this indicates that
there is a leak in the condenser unit.

Warning!

After leak-testing, unscrew special tool 64 5 121 

slowly

from special tool 64 5 122 to reduce pressure.

After leak-testing:

Replace all sealing rings and moisten with refrigerant oil

Assemble A/C system

Evacuate and fill A/C system

RA  Leak-testing condenser

BMW AG - TIS

19.01.2013  16:52

Issue status (12/2007) Valid only until next DVD is issued

Copyright

Page  - 3 -