Accumulator HVAC: Service and Repair

SUCTION ACCUMULATOR

Removal and Installation

NOTE:  Installation of a new suction accumulator is not required when repairing the air conditioning system, except when there is physical evidence of
contamination from a failed A/C compressor or damage to the suction accumulator.

1. Recover the refrigerant.
2. Disconnect the A/C cycling switch electrical connector.

3. CAUTION:  Use a back-up wrench to prevent damage to the tubes.

Disconnect the suction accumulator inlet and outlet fittings.
-

Discard the O-ring seals.

-

To install, tighten the inlet fitting to 39 Nm (29 lb-ft)

4. Remove the suction accumulator bracket screws and the suction accumulator.

5. To install, reverse the removal procedure.

-

Install new O-ring seals.

-

Lubricate the refrigerant system with the correct amount of clean PAG oil or equivalent.

6. Evacuate, leak test and charge the refrigerant system.