gmc Workshop Repair Guides

GMC Workshop Service and Repair Manuals

Diagram Information and Instructions|Page 603 > < Diagram Information and Instructions|Page 601
Page 6
background image

4. Turn ON the ignition and operate all accessories.
5. If the voltage measured is greater than 1 volt, there is a short to voltage in the circuit.

Testing for Continuity

NOTE:  Refer to Test Probe Notice in Service Precautions.

The following procedures verify good continuity in a circuit.

With a DMM
1. Set the rotary dial of the DMM to the ohms position.
2. Disconnect the power feed (i.e. fuse, control module) from the suspect circuit.
3. Disconnect the load.
4. Press the MIN MAX button on the DMM.
5. Connect one lead of the DMM to one end of the circuit to be tested.
6. Connect the other lead of the DMM to the other end of the circuit.
7. If the DMM displays low or no resistance and a tone is heard, the circuit has good continuity.

With a Test Lamp

IMPORTANT:  Only use the test lamp procedure on low impedance power and ground circuits.

1. Remove the power feed (i.e. fuse, control module) from the suspect circuit.
2. Disconnect the load.
3. Connect 1 lead of the test lamp to 1 end of the circuit to be tested.
4. Connect the other lead of the test lamp to battery positive voltage.
5. Connect the other end of the circuit to ground.
6. If the test lamp illuminates (full intensity), then the circuit has good continuity.

Testing For Electrical Intermittents

Perform the following procedures while wiggling the harness from side to side. Continue this at convenient points (about 6 inches apart) while watching
the test equipment.

-

Testing for Short to Ground

-

Testing for Continuity

-

Testing for a Short to Voltage

If the fault is not identified, perform the procedure below using the MIN MAX feature on the J 39200 DMM. This feature allows you to manipulate the
circuit without having to watch the J 39200. The J 39200 will generate an audible tone when a change is detected.

IMPORTANT:  The J 39200 must be used in order to perform the following procedure since the J 39200 can monitor current, resistance or voltage
while recording the minimum (MIN), and maximum (MAX) values measured.

1. Connect the J 39200 to both sides of a suspected connector (still connected), or from one end of a suspected circuit to the other. Refer to

Troubleshooting with a Digital Multimeter for information on connecting the J 39200 to the circuit.  See: General Electrical Diagnostic
Procedures/Circuit Testing/Digital Multimeter

2. Set the rotary dial of the J 39200 to the V (AC) or V (DC) position.
3. Press the range button of the J 39200 in order to select the desired Voltage range.
4. Press the MIN MAX button of the J 39200. The J 39200 displays 100 ms RECORD and emits an audible tone (beep).

IMPORTANT:  The 100 ms RECORD mode is the length of time an input must stay at a new value in order to record the full change.

5. Simulate the condition that is potentially causing the intermittent connection, either by wiggling the connections or the wiring, test driving, or

performing other operations. Refer to Inducing Intermittent Fault Conditions.  See: General Electrical Diagnostic Procedures/Circuit
Testing/Inducing Intermittent Fault Conditions

6. Listen for the audible Min Max Alert which indicates that a new minimum or maximum value has been recorded.
7. Press the MIN MAX button once in order to display the MAX value and note the value.
8. Press the MIN MAX button again in order to display the MIN value and note the value.
9. Determine the difference between the MIN and MAX values.

-

If the variation between the recorded MIN and MAX voltage values is 1 volt or greater an intermittent open or high resistance condition exists.
Repair the condition as necessary.

-

If the variation between the recorded MIN and MAX voltage values is less than 1 volt an intermittent open or high resistance condition does
not exist.

Testing For Intermittent and Poor Connections

Most intermittent conditions are caused by faulty electrical connections or wiring. Inspect for the following items:

-

Wiring broken inside the insulation

-

Poor connection between the male and female terminal at a connector. Refer to Testing for Proper Terminal Contact for the specific procedure.  
See: General Electrical Diagnostic Procedures/Circuit Testing/Testing For Proper Terminal Contact

Diagram Information and Instructions|Page 603 > < Diagram Information and Instructions|Page 601