Release the field coil connector from the holder, then disconnect it. Check the thermal protector for continuity. If there is no continuity, replace the
thermal protector.

NOTE:  The thermal protector will have no continuity above 251.6 to 262.4 °F (122 to 128 °C). When the temperature drops below 240.8 to 
219.8 °F (116 to 104 °C), the thermal protector will have continuity.

-

Check resistance of the field coil.
Field Coil Resistance: 3.05 to 3.35 ohms at 68 °F (20 °C)

If resistance is not within specifications, replace the field coil.