Refrigerant: Service and Repair
Evacuating the System

Evacuating the System

1. This process, the removal of unwanted air and moisture, is critical to the correct operation of the air conditioning system.

Moisture in the system can be highly destructive and may cause internal blockages due to freezing; water suspended in the lubricating oil will
damage the compressor. Once the system has been dismantled, or the refrigerant charge recovered, all traces of moisture must be removed before
recharging.

Specific procedures will vary depending on the individual characteristics of the recovery/recycle/recharge equipment, and must be carried out
exactly in accordance with the manufacturer's instructions. However, it is recommended that initially only the high-side valve be opened at the start
of the procedure. After a short time a small depression should be seen on the low-side, at which point the low-side valve may be opened and the
evacuation process completed. If a vacuum is not registered on the low-side, it may indicate that the expansion valve is permanently closed or that
the system is blocked. This simple check may save time and effort when the system is recharged.