oldsmobile Workshop Repair Guides

Oldsmobile Workshop Service and Repair Manuals

Diagram Information and Instructions|Page 1049 > < Diagram Information and Instructions|Page 1047
Page 3
background image

1. Set the rotary dial of the DMM to the V (DC) position.
2. Connect the positive lead of the DMM to one point of the circuit to be tested.
3. Connect the negative lead of the DMM to the other point of the circuit.
4. Operate the circuit.
5. The DMM displays the difference in voltage between the two points.

Testing For Continuity

NOTE:  Refer to Test Probe Notice in Cautions and Notices.

The following procedures verify good continuity in a circuit.

With a DMM
1. Set the rotary dial of the DMM to the Ohm position.
2. Disconnect the power feed (i.e. fuse, control module) from the suspect circuit.
3. Disconnect the load.
4. Press the MIN MAX button on the DMM.
5. Connect one lead of the DMM to one end of the circuit to be tested.
6. Connect the other lead of the DMM to the other end of the circuit.
7. If the DMM displays low or no resistance and a tone is heard, the circuit has good continuity.

With a Test Lamp

IMPORTANT:  Only use the test lamp procedure on low impedance power and ground circuits.

1. Remove the power teed (i.e. fuse, control module) from the suspect circuit.
2. Disconnect the load.
3. Connect one lead of the test lamp to one end of the circuit to be tested.
4. Connect the other lead of the test lamp to battery positive voltage.
5. Connect the other end of the circuit to ground.
6. If the test lamp illuminates (full intensity), then the circuit has good continuity.

Testing For Short to Ground

NOTE:  Refer to Test Probe Notice in Cautions and Notices.

The following procedures test for a short to ground in a circuit.

With a DMM
1. Remove the power feed (i.e. fuse, control module) from the suspect circuit.
2. Disconnect the load.
3. Set the rotary dial of the DMM to the Ohm position.
4. Connect one lead of the DMM to one end of the circuit to be tested.
5. Connect the other lead of the DMM to a good ground.
6. If the DMM does NOT display infinite resistance (OL), there is a short to ground in the circuit.

With a Test Lamp
1. Remove the power feed (i.e. fuse, control module) from the suspect circuit.
2. Disconnect the load.
3. Connect one lead of the test lamp to battery positive voltage.
4. Connect the other lead of the test lamp to one end of the circuit to be tested.
5. If the test lamp illuminates, there is a short to ground in the circuit.

Fuse Powering Several Loads
1. Review the system schematic and locate the fuse that is open.
2. Open the first connector or switch leading from the fuse to each load.
3. Connect a DMM across the fuse terminals (be sure that the fuse is powered).

^

When the DMM displays voltage the short is in the wiring leading to the first connector or switch.

^

If the DMM does not display voltage refer to the next step.

4. Close each connector or switch until the DMM displays voltage in order to find which circuit is shorted.

General Information

It is important to test terminal contact at the component and any in-line connectors before replacing a suspect component. Mating terminals must be
inspected to ensure good terminal contact. A poor connection between the make and female terminal at a connector may be the result of contamination or
deformation.

Contamination may be caused by the connector halves being improperly connected. A missing or damaged connector seal, damage to the connector
itself, or exposing the terminals to moisture and dirt can also cause contamination. Contamination, usually in the underhood or underbody connectors,
leads to terminal corrosion, causing an open circuit or intermittently open circuit.

Diagram Information and Instructions|Page 1049 > < Diagram Information and Instructions|Page 1047