Refrigerant Oil: Specifications
Distribution of Oil Quantity

Air Conditioning Information

Distribution of the oil quantity in the refrigerant circuit

Note:

-

Oil removed by suction must be returned to the system!

-

Refrigerant oil removed from a previously run air-conditioning system may no longer be used (special category waste)!

-

After the refrigerant has been removed by suction and a component has been replaced, the oil quantity must be determined and topped up
by the quantity remaining in the removed component!

When individual components listed in the following table are replaced, the measured oil quantity removed by suction from the refrigerant circuit
and the quantity in the component must be returned to the refrigerant circuit.

In order to use a new compressor in a refrigerant circuit that is already functional, the oil quantity for the new compressor must first be reduced by
max. 60 cubic cm. The compressor oil quantity is 140 cubic cm in the scope of delivery for a new compressor.

Climatronic (Right/Left) Basic vehicle: Distribution of oil quantity in the individual air conditioning components
Component

Oil quantity: low-pressure oil 8 in cubic cm 

Compressor

63 cubic cm

Condenser incl. dryer

28 cubic cm

Dryer cartridge, single

14 cubic cm

Intake pipe in engine compartment

14 cubic cm

Pressure line from compressor to condenser (not given)
Pressure line in engine compartment

7 cubic cm

Evaporator

28 cubic cm

Total compressor oil quantity

140 cubic cm

Component

Distribution of oil quantity in % 

Compressor

45 %

Condenser incl. dryer

20 %

Dryer cartridge, single

10 %

Intake pipe in engine compartment

10 %

Pressure line from compressor to condenser (not given)
Pressure line in engine compartment

5 %

Evaporator

20 %

Total compressor oil quantity

for 100 %

Climatronic 2+2 Vehicle with 2 + 2: Distribution of oil quantity in the individual air conditioning components
Component

Oil quantity: low-pressure oil 8 in cubic cm 

Compressor

65 cubic cm

Condenser incl. dryer

30 cubic cm

Dryer cartridge, single

15 cubic cm

Intake pipe in engine compartment

15 cubic cm

Pressure line from compressor to condenser (not given)
Pressure line in engine compartment

10 cubic cm

Front Evaporator

30 cubic cm

Rear Evaporator

30 cubic cm

Intake pipe in floor area

20 cubic cm

Intake pipe in floor area

20 cubic cm

Intake pipe for rear AC

10 cubic cm

Pressure line for rear AC

10 cubic cm

Total compressor oil quantity

240 cubic cm

Component

Distribution of oil quantity rounded off in approx. % 

Compressor

27 %

Condenser incl. dryer

13 %

Dryer cartridge, single

6 %

Intake pipe in engine compartment

6 %

Pressure line from compressor to condenser (not given)
Pressure line in engine compartment

4 %

Front Evaporator

13 %