Leon Mk2
|
Note
|
Possible deviation from specification | Possible cause of fault | Measures to be taken | ||||||||||||||||||||
|
|
| ||||||||||||||||||||
|
|
| ||||||||||||||||||||
|
|
Note
t | Clean the refrigerant circuit (rinse with refrigerant R134a or sweep with compressed air or nitrogen). |
t | Check the measured values of the evaporator output temperature sender -G263- and the actuation of the air conditioner compressor regulating valve -N280-. If measured value of evaporator output temperature sender -G263- is not OK, evaporator may ice up or cooling output may not be attained. |
t | If, after replacing the expansion valve, operation of the air conditioning system is not OK when the test is repeated (re-fit old expansion valve), clean refrigerant circuit (flush with refrigerant R134a or blow out with compressed air and nitrogen ). Replace the compressor and liquid tank. |
t | When this fault occurs, it is possible for the evaporator to ice up even when the proper quantity of refrigerant is present in the circuit. |
t | If the expansion valve is faulty (constantly closed or does not open enough), the air-conditioner compressor regulating valve -N280- is activated at maximum power, and the low pressure drops to or below the value of the diagram (the air-conditioner compressor sucks refrigerant from the low-pressure side). But, as the refrigerant cannot flow through the expansion valve, the cooling power cannot be achieved, and the pressure may also not increase or only increase slightly, seeing as there is no energy transformation. |
Possible deviation from specification | Possible cause of fault | Measures to be taken | ||||||||||
|
|
| ||||||||||
|
|
Possible deviation from specification | Possible cause of fault | Measures to be taken | ||||||||||||||||||||||||||||||||||||
|
|
|
Note
t | If this fault occurs, the evaporator may freeze in spite of the fact there is the correct amount of refrigerant in the circuit. |
t | If the expansion valve is faulty (constantly closed or does not open enough), the air-conditioner compressor regulating valve -N280- is activated at maximum power, and the low pressure drops to or below the value of the diagram (the air-conditioner compressor sucks refrigerant from the low-pressure side). But, as the refrigerant cannot flow through the expansion valve, the cooling power cannot be achieved, and the pressure may also not increase or only increase slightly, seeing as there is no energy transformation. |
Possible deviation from specification | Possible cause of fault | Measures to be taken | ||||||||||||||||
|
|
| ||||||||||||||||
|
|
Note
t | If this incident occurs only after a prolonged service period or occasionally (the low pressure drops to below the specification and the evaporator freezes), only the desiccant needs to be replaced (located in the liquid tank). The amount of refrigerant oil must be compensated for. The refrigerant circuit must now be vacuumed for at least 3 hours. |
t | In principle it is not necessary to blow out the refrigerant circuit with compressed air and nitrogen in the event of this complaint, seeing as there is generally only a small amount of humidity in the system which may be eliminated by vacuuming the circuit for a prolonged period of time. |
t | If this fault occurs, the evaporator may freeze in spite of the fact there is the correct amount of refrigerant in the circuit. |
Possible deviation from specification | Possible cause of fault | Measures to be taken | ||||||||||||||||||||||||
|
|
|
Note
t | In the case of the fault „High pressure normal, low pressure too low“, the following must be taken into account: Error, the evaporator may freeze, or the cooling power is not achieved. |
t | If this fault occurs, the evaporator may freeze in spite of the fact there is the correct amount of refrigerant in the circuit. |
t | Check the measurement value of the evaporator outlet temperature sender -G263- or the evaporator temperature sender -G308- and the controlling of the air conditioning system compressor regulating valve -N280-. If the value measured by the high-pressure sender -G65- is incorrect, the evaporator may freeze or the cooling power is not achieved. |
t | If the air-conditioner compressor regulating valve -N280- is faulty (the regulating valve is not activated, but the compressor operates correctly), it is not necessary to blow out the refrigerant circuit. In this case, replacing the air-conditioner compressor is sufficient (compensate for the amount of refrigerant oil in the new air-conditioner compressor). |
t | If the expansion valve is faulty (constantly closed or does not open enough), the air-conditioner compressor regulating valve -N280- is activated at maximum power, and the low pressure drops to or below the value of the diagram (the air-conditioner compressor sucks refrigerant from the low-pressure side). But, as the refrigerant cannot flow through the expansion valve, the cooling power cannot be achieved, and the pressure may also not increase or only increase slightly, seeing as there is no energy transformation. |
→ Rep. gr.87 |
Possible deviation from specification | Possible cause of fault | Measures to be taken | ||||||||||||||||||||||||||||||||||||
|
|
|
Note
t | If the air-conditioner compressor regulating valve -N280- is faulty (the regulating valve is not activated, but the compressor operates correctly), it is not necessary to blow out the refrigerant circuit. In this case, replacing the air-conditioner compressor is sufficient (compensate for the amount of refrigerant oil in the new air-conditioner compressor). |
t | The refrigerant circuit may be overcharged with refrigerant oil if, for example, the compressor has been replaced without compensating the amount of refrigerant oil. |
t | If the air conditioner compressor is not replaced, the refrigerant must be extracted from the compressor (replace the O-ring) via the oil drain plug. Fill the 50 grams in the → Repair Manual of the respective vehicle indicated complete refrigerant oil quantity in the air conditioner compressor and the rest in the refrigerant circuit. |
t | If the expansion valve is faulty (constantly closed or does not open enough), the air-conditioner compressor regulating valve -N280- is activated at maximum power, and the low pressure drops to or below the value of the diagram (the air-conditioner compressor sucks refrigerant from the low-pressure side). But, as the refrigerant cannot flow through the expansion valve, the cooling power cannot be achieved, and the pressure may also not increase or only increase slightly, seeing as there is no energy transformation. |
Possible deviation from specification | Possible cause of fault | Measures to be taken | ||||||||||||||||||
|
|
| ||||||||||||||||||
|
|
Note
t | Overfilling with refrigerant oil may occur if, for example, the compressor has been renewed without adjusting the quantity of refrigerant oil. |
t | If expansion valve is defective (permanently open), evaporator temperature is no longer regulated such that only refrigerant in gas form exits from the evaporator. Under certain usage conditions, liquid droplets may then be drawn in by the compressor and cause noise (liquid cannot be compressed). |
t | If there is too much refrigerant oil in the circuit, discharge compressor and renew receiver. After cleaning the refrigerant circuit (flush with refrigerant R134a or blow out with compressed air and nitrogen), add the correct amount of refrigerant oil to the circuit → Chapter. |