Bleeding coolant circuit > < Calling up fault memory of heater control unit J162
Fault table
   
Fault table
Fault code number and meaningPossible cause of faultFault rectification with remarks
000   
No malfunction  
001  
Overvoltage warning (> 16 V)ControllerRenew
002   
Undervoltage warning (< 10.2 V)2nd. batteryCharge
010  
Overvoltage shut-off (> 16 V)2nd. batteryVoltage was present for longer than 20 seconds
011  
Undervoltage shut-off (< 10.2 V)2nd. batteryVoltages were present for longer than 20 seconds
012  
OverheatingTemperature at flame monitor -G64- or overheating sensor -G189- too high (> 125 °C). Air in coolant circuit, bleed → Chapter
014  
Evaluation of temperature difference between flame monitor -G64- and overheating sensor -G189-Air in coolant circuit, flame monitor -G64- defective, overheating sensor -G189- defectiveBleed → Chapter, check flame monitor -G64- → Chapter, check overheating sensor -G189- → Chapter
015  
Continuous shut-downAir in coolant circuit,Bleed → Chapter Clear fault memory → Chapter
017  
OverheatingTemperature too high (> 130 °C) at overheating sensor -G189- and coolant temperature sender for heater -G241-Air in coolant circuit, bleed → Chapter Check overheating sensor -G189- → Chapter Check coolant temperature sender for heater -G241- → Chapter Clear fault memory → Chapter
020  
Glow plug for heater -Q9-DefectiveRenew
021  
Short circuit on the glow plug for heater -Q9-Short circuit on the connection or in the glow plugRenew if necessary.
030  
Combustion air blower -V6-BlockedRenew
032  
Combustion air blower -V6-Open circuitCheck the connection, replace if necessary
038  
Fresh air blower -V2-Open circuitCheck,
039 Renew if necessary.
Fresh air blower -V2-Short circuit 
041  
Circulation pump -V55-Open circuitCheck, replace if necessary
042 and bleed coolant circuit → Chapter
Circulation pump -V55-Short circuit 
047  
Metering pump -V54-Short circuitCheck,
048 Renew if necessary.
Metering pump -V54-Open circuit 
050  
Continuous shut-downUnsuccessful start attemptsErase fault memory → Chapter.
051  
Time overrunWhen blowing flame monitor -G64- cold with combustion air blower -V6-Check flame monitor -G64- → Chapter.
052  
Time overrunSafety time exceeded after several start attemptsCheck: exhaust pipe fuel volume, combustion air induction
053   
Flame failure from the high control levelMetering pump -V54- (quantity delivered) Exhaust pipe (blocked) Combustion air (insufficient) Check,
054Flame monitor -G64- (values) Replace if necessary → Chapter
Flame failure from medium control levelThe fault memory is cleared if the start is successful.  
056 Heater is permanently switched off.  
Flame failure from low control levelClear fault memory after checking and replacing.Switch on heater once again.
060  
Coolant temperature sender for heater -G241-Open circuitCheck water temperature,
061 Check coolant temperature sender for heater -G241-,
Coolant temperature sender for heater -G241-Short circuitReplace if necessary → Chapter
064  
Flame monitor -G64-Open circuitFlame monitor -G64-
065 Checking → Chapter
Flame monitor -G64-Short circuit 
071  
Overheating sensor -G189-Open circuitCheck,
072  
Overheating sensor -G189-Short circuitReplace if necessary → Chapter
090  
Heater control unit -J162-Error in microprocessor, (memory present)Replace if necessary → Chapter
091  
Interference voltageIn vehicle electrical system or other voltage sourcesRectify
092 to 103  
Heater control unit -J162-DefectiveReplacing → Chapter.

   