Tribeca F6-3.6L (2008)
5. After the low-pressure gauge reaches 100.0 kPa (750 mmHg, 29.5 in Hg) or higher, evacuate the system for approx. 15 minutes. (Continue
evacuation).
6. After 15 minutes of evacuation, if the reading shows 100.0 kPa (750 mmHg, 29.5 in Hg) or higher, close the valves on the both sides to stop the
vacuum pump.
7. Note the low-pressure gauge reading.
8. Leave it at least 5 minutes, and then check the low-pressure gauge reading for any changes. If the gauge indicator shows near zero point, it is a
sign of leakage. Check pipe connector points, repair them, and make sure there is no leakage.
9. Follow the can tap operation manual, install to the refrigerant can.