Astra
Note:
The IDLE CO POT. has a permissible adjustment range of 0.25 to 4.81 V. If the value lies outside this range, a trouble code will be set.
Using the IDLE CO POT., the injection time can be directly influenced over the whole load range. If there are deviations, observe the O2 INTEGRATOR as well. Turning potentiometer towards right (increased voltage) means an increase of the injection time (CO % increases). A turn to the left means a reduction in the injection time (CO % decreases).
Example: Adjustment to 0.1 V: injection time is increased by 0.25 ms Adjustment to 4.0 V: injection time is decreased by 0.25 ms
There is therefore a total adjustment in injection time of max. 0.5 ms.
* only for 20 XE/20 XEJ engines
Trouble-shooting: Nominal Value: Cause of Fault: (If nominal value is not attained)
The relevant terminal designations are under the mass air flow sensor plug insulation.
If the nominal values are attained -----> IDLE CO POT. in mass air flow sensor defective
Checking the IDLE CO POT.: Ignition OFF · With multimeter between Ter. 2 and · Potentiometer defective Ter. 6 (IDLE CO POT. signal lead): Potentiometer at left stop: 0 to 30 Ohm Potentiometer at right stop: 900 to 1100 Ohm
Important:
With closed loop systems, ensure that the idle CO potentiometer is on a medial value of 1.4 V. If a deviation is present which cannot be regulated by the oxygen sensor, this may be indicated by incorrect mixture integrator values or by storage of trouble codes 44 and 45.
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|