Display zone | Significance | Explanatory notes |
1 | Actual feedback value of air flow flap control motor potentiometer -G113- (in air flow flap control motor -V71-) | l
| Display value greater than “9” and less than “251” |
l
| Maximum permissible deviation “3” units from specified feedback value (in range greater than “10” but less than “190”) |
|
2 | Specified feedback value for air flow flap control motor potentiometer -G113- (calculated by operating and display unit, Climatronic control unit -J255-) | l
| Display range “10 ... 245” |
|
3 | Value determined during “Basic setting” and stored in the operating and display unit, Climatronic control unit -J255- for the air flow flap control motor potentiometer -G113- with control motor set to “Lower stop” (air flow/fresh-air flaps closed, recirculated-air mode) | l
| Display value greater than “9” and less than “71” |
|
4 | Value determined during “Basic setting” and stored in the operating and display unit, Climatronic control unit -J255- for the air flow flap control motor potentiometer -G113- with control motor set to “Upper stop” (air flow/fresh-air flaps open) | l
| Display value greater than “189” and less than “246” |
|