After filling, remove quick-connect coupling (1) and if necessary
use the cleaning agent contained in the special tool case to clean
up the UV additive.

Further tasks:

Start engine.

Run A/C system at highest setting for 5-10 minutes in order to

ensure adequate distribution of dye in the system

Switch off engine

Check all A/C system components for possible leaks

Possible leaks show up in luminous green

Complete accompanying information label (1) with the relevant
data and attach in an easily visible position next to the filling
capacity information label (2).