isuzu Workshop Repair Guides

Isuzu Workshop Service and Repair Manuals

Leak Check - Repair of Refrigerant Leaks|Page 1112 > < Leak Check - Repair of Refrigerant Leaks|Page 1110
Page 5
background image

7.  Check to ensure that the pressure does not change after 10 minutes or more.

If the pressure changes, check the system for leaks.

If leaks occur, retighten the refrigerant line connections and repeat the evacuation steps.

8.  If no leaks are found, again operate the vacuum pump for 20 minutes or more. After confirming that the gauge manifold pressure is at 750 mm Hg

(30 in Hg), close both hand valves.

9.  Close positive shutoff valve. Stop the vacuum pump and disconnect the center hose from the vacuum pump.

Charging the Refrigerant System

There are various methods of charging refrigerant into the air conditioning system.

These include using J-39500 (ACR4: HFC-134a Refrigerant Recovery/Recycling/Recharging/System) or equivalent and direct charging with a weight
scale charging station.

Charging procedure

ACR4 (or equivalent) method

For the charging of refrigerant recovered by ACR4 (or equivalent), follow the manufacturer's instruction.

Leak Check - Repair of Refrigerant Leaks|Page 1112 > < Leak Check - Repair of Refrigerant Leaks|Page 1110