System Relay, HVAC > < Control Module HVAC|Description and Operation
Page 2
background image

-

Blower speed control to minimize the effects of ram air. Road speed compensation is inhibited when maximum cooling LO, or maximum
heating HI, is selected; also inhibited in defrost mode with airflow set to maximum.

-

Used to determine the frequency at which the exterior temperature display is updated.

3. Coolant temperature (signal derived from ECM via instrument cluster):

-

Input from the heater matrix temperature sensor used to control water valve and thus vent temperatures.

-

Used to monitor the temperature of coolant at the heater matrix to assist the control of air outlet temperature.

-

Used to inhibit the blowers when heating is selected and the engine coolant temperature is below 30 °C.

-

Is used to provide progressive increase in blower speed up to 60 °C.

-

To inhibit the water valve and pump when the coolant temperature is < 10 °C

4. Compressor ON signal:

-

Input to the A/CCM from the compressor relay output.

-

Used to determine compressor fault conditions.