| The duty signal is the result of the relationship between the width of the pulse -A- and the length of the signal -B-. |
–
| Depending on the adjustment in the Climatronic control unit -J255-/Air conditioning control unit -J301- and the magnitudes of the environment conditions measured, the amplitude of the rectangular wave signal (duty cycle between 100% and more than 30%, the regulation valve is activated in such a way that enough power is directed to the compressor to reach the specified temperatures). |
Note t
| When the temperature setting is the lowest, the Compressor regulation valve -N280- is activated so that the maximum current of about 0.65 A flows across the Compressor regulation valve, air conditioning -N280- (maximum compressor performance). |
t
| In control mode; duration of activation depends on the required cooling output, the vehicle voltage etc. The activation will last, however, until at least a current flow of 0.3 A is reached. |
|
|
|