The voltage signal must fluctuate between the ranges 0.0...+0.3 und +0.7...+1.0 V when introducing the control. |
Voltage values greater than +0.7 V mean a richer mixture composition (less oxygen in the exhaust) |
Voltage values less than +0.3 V mean a leaner mixture composition (more oxygen in the exhaust) |
–
| If a poor vehicle handling occurs before inserting the lambda control, the lambda control cannot be the cause of the fault. |
–
| If a poor vehicle handling occurs only after inserting the lambda control, check operation → Chapter. |
Note t
| If the poor handling has improved after inserting the control, the cause of the fault (e.g. unmetered air, defective injection valve, etc..) is eliminated by engaging the control. This can be detected by reading out the lambda learned values. |
t
| Read measured value block (function 08) and select display group 008. If the specified values are not reached, eliminate fault. |
t
| In addition, read out the measured value blocks in the function 04 (basic setting). For this function, the activated charcoal filter system solenoid valve 1 -N80- is closed. |
t
| The lambda control can be switched off and on with the help of the display group 099. It can be switched back and forward between “Basic setting” (lambda control off) and “Read measured value block” (lambda control on) by pressing the buttons 4 or 8. |
|
|
Reading measured value block 7 -> | 1 0.780V 3 4 |
|