WARNING Danger of freezing injuries. |
If refrigerant circuit has not been evacuated, refrigerant and refrigerant oil will escape. |
Extract refrigerant before opening refrigerant circuit. If the refrigerant circuit is not opened within 10 minutes after it has been evacuated, pressure may develop in coolant circuit due to re-evaporation. Extract refrigerant again. |
|
–
| Evacuate refrigerant circuit, e.g. with air conditioner service station -VAS 6007A- (or later model) before renewing valve -2-. |
–
| Unscrew valve core -2- (2 ± 0.2 Nm) out of refrigerant line using suitable adapter -4-. When doing this, carefully hold valve support -1- with a suitable tool. |
|
|
|