Note t
| The signal ratio for the time is displayed in display zone “3” whilst the signal is actually present. |
t
| The operating and display unit for air conditioner/Climatronic -E87- calculates the pressure in the refrigerant circuit via the signal ratio. The calculated pressure is displayed in display zone “4”. |
t
| At a signal ratio of less than 12.5% (corresponds to approx. 1.5 bar absolute) and greater than 87.5% (corresponds to approx. 32 bar absolute), the operating and display unit for air conditioner/Climatronic -E87- does not switch on the compressor (the air conditioner compressor regulating valve -N280- is not actuated). The compressor is only reactivated once the signal ratio exceeds 12.5% (corresponding to an absolute pressure of 1.5 bar) or drops below 84% (corresponding to an absolute pressure of 29 bar). |
t
| In order to prevent abrupt compressor shut-off on account of excessive pressure in the refrigerant circuit or an excessive coolant temperature, the compressor output is reduced by the operating and display unit for air conditioner/Climatronic -E87-: |
t
| - As soon as the pressure in the refrigerant circuit exceeds 30 bar (absolute) (full compressor output is not released again until the pressure has dropped below 27 bar). |
t
| - As soon as the coolant temperature exceeds 115° C (it is shut down completely at 118° C). |
t
| At a signal ratio of approx. 47% (equivalent to an absolute pressure of 16 bar in the refrigerant circuit), the operating and display unit for air conditioner/Climatronic -E87- sends a signal to the control unit for the radiator fans -J293-, thereby switching the radiator fan -V7- to speed 2. The signal remains on until the signal ratio has fallen below approx. 40% (equivalent to an absolute pressure of approx. 13 bar). |
t
| An absolute pressure of 0 bar represents an absolute vacuum. Therefore normal ambient pressure is equivalent to approx. 1 bar absolute. On the dials of most pressure gauges 0 bar is equivalent to an absolute pressure of one bar (recognisable by the datum -1 below 0). |
t
| The pressure in the refrigerant circuit and therefore the signal ratio depends on various factors. In general, however, at maximum compressor output and an ambient temperature of 20 to 25 °C, the pressure should not exceed 20 bar (absolute). Under extreme conditions of use (e.g. in hot countries with high ambient temperatures, “stop and go traffic” and high relative humidity), the extremely high refrigeration capacity involved may also result in pressures of up to 30 bar (absolute). |
t
| The high-pressure sender operates at a frequency of 50 Hz (50 Hertz = 50 cut-in pulses per second). The signal ratio indicates the proportion of cut-in time per pulse. |
t
| The cut-in signal from the high-pressure sender -G65- can be tested, for example, with the vehicle diagnostic, testing and information system -VAS 5051- in the measuring instrument function → Chapter. |
t
| The signal generated by the high-pressure sender -G65- is also used for engine control (the required compressor drive torque is governed by the refrigerant circuit pressure). Depending on the engine control unit version, the signal is displayed as a signal ratio in the measured value block. |
t
| The signal transmitted at a refrigerant circuit pressure of approx. 6 bar absolute is equivalent to a signal ratio of approx. 22% (automatic adjustment with the compressor at a standstill, at an ambient temperature of 20 °C, and with a properly filled refrigerant circuit). |
|
|
|