Check for possible leaks in the refrigerant circuit > < Cleaning the inner side of the refrigerant circuit
Application of the flush kit with adaptersSAT 4009
Application of the flush kit with adapters-SAT 4009-
   
l  Depending on the type of tools chosen, there may be differences in the work process. The specific handling instructions for each tool or adapter must be taken into account.
  WARNING
It is recommended that you always have an eye-bath ready for use in case it is needed.
If the refrigerant comes into contact with the eyes, immediately begin thorough rinsing of the eyes for 15 minutes.
Then, apply eye drops and seek medical assistance even if the eyes do not cause any pain.
Always inform the doctor of the type of refrigerant involved.
  WARNING
Before installation, the air-conditioning station should be disconnected from the electricity supply.
  E00-10263
–  Connect the red tube (high-pressure area)-1-, on the side of the valve rod, to the station coupling-2- after removing the plastic cap.
  E00-10257
–  Connect the other end of the red tube to the part of circuit to be cleaned, using the kit SAT 4009 and the elements required for the work.
  E00-10258
The universal bridge -1- is an example of connection, with the rubber joint -2- connected to the tube diameter.
  E00-10260
On the low pressure side (blue tube) -1- the refrigerant flows through the air conditioning circuit to be cleaned in liquid form and follows the connection to the cleaning filter.
At the input -1- the refrigerant flows, by the spy hole -3- where the level of impurities can be observed.
–  This filter removes the particles from the refrigerant which is then returned to the machine by the rapid connection -2- .
  E00-10259

Check for possible leaks in the refrigerant circuit > < Cleaning the inner side of the refrigerant circuit