Result
|
Cause Of Fault
|
E001
|
Result: System Overload
|
- A temporary current overload in the system behind fuse FE4 has occurred
Note:
In case of a temporary current overload, the cause for the blow of the fuse may be located in a circuit behind the control unit/component.
These circuits should be checked additionally for short to ground.
|
|
E002
|
Result: Defective Component
|
- If the nominal value is reached during one of the measurements, the component/control unit that has been disconnected immediately before that measurement is defective.
|
|
E003
|
Result: Short to Ground
|
- Short circuit to ground between:
X125 Underhood Electronic Module Socket Terminal 32 (XE2) & A1_A60 Controls - Heating/Air Conditioning Wiring harness connector (wiring harness side) terminal 5 (XC41)
or
- Defective component:
A1_A60 Controls - Heating/Air Conditioning
Note:
If the defective component is a control unit, the cause for the fault may be located in a circuit behind that component.
|
|
E004
|
Result: Defective Component
|
- Defective component:
K15_X125 Relay - Blower, Passenger Compartment or X125 Underhood Electronic Module
Important:
Reset the concerned control unit with the diagnostic tester before replacing it. In order to do that, call up the "RESET" function from the PROGRAMMING menu of the current system on the diagnostic tester.
Note:
The replacement of the components must be done in the listed order.
The system must be checked for proper operation after every replacement.
|
|