01 Introduction02 General information03 Information04 Maintenance05 Engine - K806 Engine - K1607 Engine - K16 with VVC08 Engine - L Series09 Emission control10 Engine management system - MEMS11 Engine management system - EDC12 Fuel delivery system13 Cooling system - K Series14 Cooling system - L Series15 Manifold & exhaust systems16 Clutch17 Manual gearbox - R6518 Manual gearbox - PG119 Automatic gearbox - CVT20 Automatic gearbox21 Drive shafts22 Steering23 Front suspension24 Rear suspension25 Brakes26 Restraint systems27 Body28 Heating & ventilation29 Air conditioning30 Wipers & washers31 Electrical32 Instruments
Rover 200 Workshop Manual (1995-1999)29 · Air conditioning
29 · Heating & A/C

Air conditioning (Performance Guide-lines): Adjustments

Make
Rover
Model
200 Workshop Manual
Year
1995–1999
Section
Adjustments › Performance Guide-lines
Air conditioningPerformance Guide-lines

Performance Guide-lines

Carry out this test with bonnet, doors or windows open; air conditioning switched on, temperature control set to cold, face vent mode and blower at maximum speed. Set the air supply control to supply fresh air.

  1. Close low pressure valve on Refrigerant Station.
  2. Close high pressure valve on Refrigerant Station.
  3. Connect Refrigerant Station to the high and low pressure servicing connections.
  4. With a thermometer measure the air intake temperature, close to the outside air inlet at the plenum.
  5. With a thermometer measure the air outlet temperature, at the centre vent outlet.
  6. Run the engine at idle speed for 10 minutes or until normal operating temperature is reached.
  7. Read both pressure gauges and thermometers. Check readings against the guide-lines shown in the table below.
Ambient Temperature °C
20 - 2425 - 2930 - 3435 - 40
Intake Temperature (˚C)35 - 3733 - 4044 - 4646 - 45
Outlet Temperature (˚C)11 - 1313 - 1516 - 2118 - 20
Low Pressure (Bar)2.5 - 2.682.66 - 2.762.88 - 3.163.06 - 3.25
High Pressure (Bar)18.75 - 18.3218.14 - 17.8918.41 - 18.9718.51 - 19.83

NOTES

  • The temperatures and pressures may be slightly increased for high humidity conditions.
  • The varying air conditioner pressure will dictate whether the fans operate in series or parallel, which will itself cause the temperatures and pressures to fluctuate. Fans could operate as follows:
  1. Condenser and cooling fan both running at half speed (series).
  2. Condenser and cooling fan both running at full speed (parallel).
  3. Fans switching from series to parallel.