CONNECT MANIFOLD GAUGE SET

1984 LJ70 RJ70 Repair Manual 38261E: diagram
1984 LJ70 RJ70 Repair Manual 38261E: diagram
1984 LJ70 RJ70 Repair Manual 38261E: diagram

AIR CONDITIONING SYSTEM — Refrigeration System

CONNECT MANIFOLD GAUGE SET TO

COMPRESSOR

2.

PLACE FREE END OF CENTER HOSE IN A SHOP 3

TOWEL

DISCHARGE SYSTEM

3.

(a) Slowly open the high pressure hand valve to adjust the refrigerant flow. Do not open the valve very much.

CAUTION: If refrigerant is allowed to escape too fast, compressor oil will be drawn out of the system.

Check the shop towel to make sure no oil is being dis-

(b) charged. If oil is present, partially close the hand valve.

After the manifold gauge reading drops below 3.5

(c) kg/cm? (50 psi, 343 kPa), slowly open the low pres- sure valve, | (d) As the system pressure drops, gradually open both high and low valves until both gauges read 0 kg/cm? (0 psi, O kPa).

Evacuating and Charg

g of

Refrigeration System

NOTE: © Whenever the air conditioning system has been exposed to the atmosphere, it must be evacuated, © After installation of a component, the system should be evacuated for approximately 15 minutes. A component in service that has been opened for repair should be evacuated for 30 minutes. 1,

EVACUATE SYSTEM

(a) Connect the manifold gauge set. (See page AC-12) (b) Install the center hose of the gauge set to the vacuum pump inlet. Run the vacuum pump, and then open both hand (c) valves. (d) After about ten minutes, check that the low pressure gauge indicates more than 600 mmHg (23.62 in.Hg, Compressor

80.0 kPa) of vacuum pressure.

corse | If the reading is not more than 600 mmHg (23.62 in.Hg,

80.0 kPa), close both valves and stop the vacuum pump. Check the system for leaks and repair as necessary. If no leaks are found, continue evacuating the system. (e) After the low pressure gauge indicates more than 700 mmHg (27.56 in.Hg, 93.3 kPa) of vacuum, continue evacuating for 15 minutes. (f) Close both hand valves, and stop the vacuum pump. Disconnect the hose from the vacuum pump. The system is now ready for charging.