Cleaning the refrigerant circuit (routine “2”)
- Make
- Audi
- Model
- Q7 Mk2
- Year
- 2015–2023
- Section
- Refrigerant circuit › Cleaning the refrigerant circuit (routine “2”)
Cleaning the refrigerant circuit (routine “2”)
Note
- In this flushing process, the high-voltage battery heat exchanger are cleaned and, once again, the condenser with receiver, part of the valve block and the associated refrigerant lines.
- The preparatory work for cleaning the refrigerant circuit has been carried outChapter“Preparatory work for cleaning the refrigerant circuit”.
- Flushing routine “1” has been successfully performed and completed → Chapter.
Initiate air conditioner basic settings via the thermal management control unit J1024 and use a routine stored there to open or close the electrically operated valves for the second flushing process (flushing routine “2”), see illustrations below and Vehicle diagnostic tester in “Guided Fault Finding” mode.
Note
- If the various electrically operated valves in the valve block ( N640, N641 N642 and N643) are not open or closed as specified, it is not possible to clean all the components installed in the refrigerant circuit. The same applies to the electrically operated valve N636 installed in the plenum chamber.
- If the various manual shut-off valves installed are not in the correct position during flushing, it is not possible to clean all the components installed in the refrigerant circuit.
- If one of the valves in the refrigerant circuit does not open or close correctly, the flushing process and subsequent evacuation of the refrigerant circuit may take considerably longer or, depending on the flowrate of the valve in question, may not be possible in the intended manner.
Close or open the shut-off valves installed in the flushing circuit as shown in the illustrations below.
Note
- The illustrations below only apply to components that are directly affected by the flushing process, for all components not described Chapter“System overview - refrigerant circuit on vehicles with high-voltage system (Audi Q7 e-tron)”.
- The colour of the lines in the illustrations below indicates which components are flushed (red lines) due to the different valve positions, which are only filled with refrigerant (green lines) and which are not affected (blue lines).
Components in the plenum chamber

Components in engine compartment

Note
- The N642(7) can be open or closed in this routine; since the N643(8) and the manual shut-off valve (6) are closed, this has no major influence on the flushing process.
Select “Flush air conditioner” routine on the connected air conditioner service station, and start routine.
Note
- Note the instructions in the associated operating instructions.
- For information on the flushing process, see Air conditioner with refrigerant R134aRep. gr.87Refrigerant circuit (Cleaning refrigerant circuit with refrigerant R134a)
Wait until the entire flushing process of the air conditioner service station has been performed and is complete.
Note
- The end of the flushing process is displayed on the air conditioner service station.
- The flushing process is complete when the air conditioner service station has extracted the refrigerant from the flushing circuit after the final flushing cycle.
- If, due to an improperly closed valve, refrigerant reaches areas it is not actually intended to reach in this flushing routine (areas indicated by blue lines), it can take a very long time to extract all refrigerant from the flushing circuit. You can recognise a valve that does not close correctly e.g. by the fact that this valve cools down due to slowly evaporating refrigerant. The valve then constricts the flow. In this case, open all manually operated shut-off valves and, if necessary, switch on the air conditioner service station again, extract the remaining refrigerant from the flushing circuit and evacuate the circuit once more.
Warning If the flushing process is interrupted or the cleaning process is not continued when this routine has ended, there is a risk of refrigerant escaping under pressure, frostbite on skin and other parts of the body.
- Before removing flushing circuit components or detaching refrigerant lines, open all shut-off valves installed in the flushing circuit.
- Initiate air conditioner basic settings via the thermal management control unit J1024 and use a routine stored there to open the various electrically operated valves Vehicle diagnostic testerin “Guided Fault Finding” mode.
- Check the pressure in the flushing circuit using the air conditioner service station. If necessary, extract any remaining refrigerant and open the flushing circuit immediately afterwards.
Parts & tools for this job For 2015 Audi Q7
- TOOLA/C manifold gauge setSearch: AC manifold gauge set
- TOOLUV leak detection kitSearch: AC UV leak detection kit
- PARTCabin filterSearch: Audi Q7 2015 cabin filter
As an Amazon Associate we earn from qualifying purchases.