Cleaning the refrigerant circuit (routine “3”)
Note
- In this flushing process, the heat exchanger for heat pump operation, the receiver, part of the valve block and the associated refrigerant lines are cleaned.
- To achieve the highest possible flow velocity, the refrigerant is conveyed through the high-voltage battery heat exchanger and the evaporator.
- The preparatory work for cleaning the refrigerant circuit has been carried outChapter“Preparatory work for cleaning the refrigerant circuit”.
- Flushing routine “2” has been successfully performed and completed → Chapter.
Initiate air conditioner basic settings via the thermal management control unit J1024 and use a routine stored there to open or close the electrically operated valves for the third flushing process (flushing routine “3”), see illustrations below and Vehicle diagnostic tester in “Guided Fault Finding” mode.
Note
- If the various electrically operated valves in the valve block ( N640, N641 N642 and N643) are not open or closed as specified, it is not possible to clean all the components installed in the refrigerant circuit. The same applies to the electrically operated valve N636 installed in the plenum chamber.
- If the various manual shut-off valves installed are not in the correct position during flushing, it is not possible to clean all the components installed in the refrigerant circuit.
- If one of the valves in the refrigerant circuit does not open or close correctly, the flushing process and subsequent evacuation of the refrigerant circuit may take considerably longer or, depending on the flowrate of the valve in question, may not be possible in the intended manner.
Close or open the shut-off valves installed in the flushing circuit as shown in the illustrations below.
Note
- The illustrations below only apply to components that are directly affected by the flushing process, for all components not described Chapter“System overview - refrigerant circuit on vehicles with high-voltage system (Audi Q7 e-tron)”.
- The colour of the lines in the illustrations below indicates which components are flushed (red lines) due to the different valve positions, which are only filled with refrigerant (green lines) and which are not affected (blue lines).
Components in the plenum chamber

Components in engine compartment

Note
- Different valve block flows are possible during the flushing process, depending on the software of the thermal management control unit J1024, by changing the position of shut-off valves (7, 8, 10, 11). The position of the shut-off valves cannot be changed manually.
- In version “1” of the J1024, the shut-off valves are open or closed for the flushing process as shown above (shut-off valve (11) open and shut-off valves (7, 8,10) closed).
- In version “2” of the J1024, the shut-off valves of J1024 are in a different position (contrary to the illustration above, shut-off valve (11) is closed and shut-off valves (7, 8, 10) are open). In this position, refrigerant also flows into the condenser (3) during the flushing process (and from there into the mounted receiver). Consequently, extraction of the refrigerant (and therefore the entire flushing process) takes somewhat longer.
Select “Flush air conditioner” routine on the connected air conditioner service station, and start routine.
Note
- Note the instructions in the associated operating instructions.
- For information on the flushing process, see Air conditioner with refrigerant R134aRep. gr.87Refrigerant circuit (Cleaning refrigerant circuit with refrigerant R134a)
Wait until the entire flushing process of the air conditioner service station has been performed and is complete.
Note
- The end of the flushing process is displayed on the air conditioner service station.
- The flushing process is complete when the air conditioner service station has extracted the refrigerant from the flushing circuit after the final flushing cycle.
- If, due to an improperly closed valve, refrigerant reaches areas it is not actually intended to reach in this flushing routine (areas indicated by blue lines), it can take a very long time to extract all refrigerant from the flushing circuit. You can recognise a valve that does not close correctly e.g. by the fact that this valve cools down due to slowly evaporating refrigerant. The valve then constricts the flow. In this case, open all manually operated shut-off valves and, if necessary, switch on the air conditioner service station again, extract the remaining refrigerant from the flushing circuit and evacuate the circuit once more.
Warning If the flushing process is interrupted or the cleaning process is not continued when this routine has ended, there is a risk of refrigerant escaping under pressure, frostbite on skin and other parts of the body.
- Before removing flushing circuit components or detaching refrigerant lines, open all shut-off valves installed in the flushing circuit.
- Initiate air conditioner basic settings via the thermal management control unit J1024 and use a routine stored there to open the various electrically operated valves Vehicle diagnostic testerin “Guided Fault Finding” mode.
- Check the pressure in the flushing circuit using the air conditioner service station. If necessary, extract any remaining refrigerant and open the flushing circuit immediately afterwards.